head_banner

Factory Supply Inline Electromagnetic Flow Meter - SUP-LDGR Electromagnetic BTU meter – Sinomeasure

Factory Supply Inline Electromagnetic Flow Meter - SUP-LDGR Electromagnetic BTU meter – Sinomeasure

short description:


Product Detail

Product Tags

Related Video

Feedback (2)

In order to give you convenience and enlarge our business, we also have inspectors in QC Team and assure you our best service and product for Inline Ph Meter, Ultrasonic Level Sensor Price, Tds Meter Price Online, We welcome you to definitely inquire us by simply call or mail and hope to develop a prosperous and cooperative connection.
Factory Supply Inline Electromagnetic Flow Meter - SUP-LDGR Electromagnetic BTU meter – Sinomeasure Detail:

  • Specification
 Product  Electromagnetic BTU meter
 Model  SUP-LDGR
 Diameter nominal  DN15 ~DN1000
 Accuracy  ±2.5%,(flowrate=1m/s)
 Working pressure  1.6MPa
 Liner material  PFA, F46, Neoprene, PTFE, FEP
 Electrode material  Stainless steel SUS316, Hastelloy C, Titanium,
 Tantalum, Platinum-iridium
 Medium temperature  Integral type: -10℃~80℃
 Split type: -25℃~180℃
 Power supply  100-240VAC,50/60Hz, 22VDC—26VDC
 Electrical conductivity  > 50μS/cm
 Ingress protection  IP65, IP68

 

  • Principle

SUP-LDGR electromagnetic BTU meter(Heat meter) operating principle: Hot (cold) water supplied by a heat source flows into a heat exchange system at a high (low) temperature(a radiator, heat exchanger, or complex system consisting of them),Outflow at low (high) temperature, in which heat is released or absorbed to the user through heat exchange (note: this process includes energy exchange between heating system and cooling system).When water flow through the heat exchange system, according to the flow sensor of flow and matching the temperature of the sensor is given for the return water temperature, and flow through time, through the calculation of the calculator and display the system heat release or absorption.
Q =   ∫(τ0→τ1) qm × Δh ×dτ =∫(τ0→τ1) ρ×qv×∆h ×dτ
Q :Heat released or absorbed by the system,JorkWh;
qm:Mass flow of water through a heat meter,kg/h;
qv:Volume flow of water through the heat meter,m3/h;
ρ:The density of water flowing through the heat meter,kg/ m3;
∆h:The difference in enthalpy between inlet and outlet temperatures of the heat
exchange system,J/kg;
τ:time,h.

Noted: the product strictly prohibited to be used in explosion-proof occasions.


Product detail pictures:

Factory Supply Inline Electromagnetic Flow Meter - SUP-LDGR Electromagnetic BTU meter – Sinomeasure detail pictures

Factory Supply Inline Electromagnetic Flow Meter - SUP-LDGR Electromagnetic BTU meter – Sinomeasure detail pictures


Related Product Guide:

To be a result of ours specialty and repair consciousness, our corporation has won an excellent reputation amongst customers all around the entire world for Factory Supply Inline Electromagnetic Flow Meter - SUP-LDGR Electromagnetic BTU meter – Sinomeasure , The product will supply to all over the world, such as: European, Mauritius, Canberra, Our company abides by the management idea of "keep innovation, pursue excellence". On the basis of assuring the advantages of existing products, we continuously strengthen and extend product development. Our company insists on innovation to promote the sustainable development of enterprise, and make us become the domestic high-quality suppliers.
  • We have been appreciated the Chinese manufacturing, this time also did not let us disappoint,good job!
    5 Stars By Olivia from Georgia - 2018.12.11 11:26
    The company's products can meet our diverse needs, and the price is cheap, the most important is that the quality is also very nice.
    5 Stars By Abigail from Russia - 2017.11.11 11:41